Fluke 1623 GEO Earth Ground Tester Kit

Fluke 1623 GEO Earth Ground Tester Kit

Our Item Number: E608-1245
Manufacturer: Fluke Corporation
Manufacturer Item #: 2571245
Product Type: Grouond Resistance Testers


Buy Now!

The Fluke 1632 Kit is all you need for advanced Earth Ground Testing!

Features & Applications:

The Fluke 1623 is a distinctive earth ground tester that can perform all four types of earth ground measurement. Specifically, the tester is able to measure earth ground loop resistances using only clamps – called Stakeless testing. This method doesn't require the use of earth ground stakes or the disconnection of ground rods.

Testing Methods:

  • 3- and 4-Pole Fall of Potential – standard earth ground testing using two ground stakes
  • 4-Pole Soil Resistivity testing – determine soil resistivity using four ground stakes
  • Selective testing – without disconnecting ground rods, a technician can measure ground resistance using a combination of stakes and a clamp.
  • Stakeless testing – innovative solution using only clamps, instead of ground stakes, to measure earth ground loop resistance.

Features:

  • 3- and 4-pole earth ground measurement
  • 4-Pole soil resistivity testing
  • 2-pole resistance measurement AC
  • 2- and 4-pole resistance measurement DC
  • Selective testing, no disconnection of ground conductor (1 clamp)
  • Stakeless testing, quick ground loop testing (2 clamps)
  • Measuring voltage switchable 20/48V
  • Programmable limits, settings
  • Continuity with buzzer
  • One-button measurement concept
  • Measuring frequency 128 Hz
  • Includes:
    • Fluke 1623 tester
    • 2 test leads
    • 4 earth ground stakes
    • 3 cable reels with wire (2-25 m, 1-50 m)
    • 2 clamps (one inducing, one sensing)
    • Batteries
    • Users manual
    • Rugged carrying case

Spec Summary:

RA 3-pole ground resistance measurement (IEC 1557-5)

Measuring Voltage:

Vm = 48 V ac

Short circuit current:

> 50 mA

Measure frequency:

128 Hz

Resolution:

0.001 Ω to 10 Ω

Measuring range:

0.001 Ω to 19.99 kΩ

Intrinsic error:

± (2 % of reading + 3 digit)

Operating error:

± (5 % of reading + 3 d)
RA 4-pole ground resistance measurement (IEC 1557-5)
Measuring Voltage:
Vm = 48 V ac
Short circuit current:
> 50 mA
Measure frequency:
128 Hz
Resolution:
0.001 Ω to 10 Ω
Measuring range:
0.001 Ω to 19.99 kΩ
Intrinsic error:
± (2 % of reading + 3 d)
Operating error:
± (5 % of reading + 3 d)
RA 3-pole ground resistance measurement with current clamp
Measuring Voltage:
Vm = 48 V ac
Short circuit current:
> 50 mA
Measure frequency:
128 Hz
Resolution:
0.001 Ω to 10 Ω
Measuring range:
0.001 Ω to 19.99 kΩ
Intrinsic error:
± (7 % of reading + 3 d)
Operating error:
± (10 % of reading + 5 d)
RA 4-pole selective ground resistance measurement with current clamp
Measuring Voltage:
Vm = 48 V ac
Short circuit current:
> 50 mA
Measure frequency:
128 Hz
Resolution:
0.001 Ω to 10 Ω
Measuring range:
0.001 Ω to 19.99 kΩ
Intrinsic error:
± (7 % of reading + 3 d)
Operating error:
± (10 % of reading + 5 d)

Stakeless ground loop measurement
Measuring Voltage:
Vm = 48 V ac
Measure frequency:
128 Hz (125 Hz on request)
Noise current (Iext):
Max. Iext = 10 A (ac) (RA < 20 Ω)
Max. Iext = 2 A (ac) (RA < 20 Ω)
Resolution:
0.001 Ω to 0.1 Ω
Measuring range:
0.001 Ω to 199.9 kΩ
Intrinsic error:
± (7 % of reading + 3 d)
Operating error:
± (10 % of reading + 5 d)
Environmental Specifications
14 to 122°F (-10 to +50°C)
32 to 95°F (0 to +35°C)
64.4 to 82.4°F (+18 to +28°C)
-4 to 140 °F (-20 to +60 °C)
C1 (IEC 654-1), 23 to 113°F (-5 to + 45°C), 5 to 95 % RH
IP56 for case, IP40 for battery door according to EN 60529
Safety Specifications
Safety Rating:
CAT II, 300 V
Mechanical & General Specifications
Display:
1999 digit LCD – display with special symbols, digit height 25 mm, fluorescent backlight
Size:
5.23" x 7.36" x 9.84" (133 x 187 x 250 mm)
Weight:
1.1 kg (including batteries)
Warranty:
Two years
Battery Life:
Typical 3000 measurements